Endress+Hauser
Endress+Hauser TH11 Modular RTD thermometer, US style
REQUEST A QUOTE
Accuracy | class A acc. to IEC 60751 class B acc. to IEC 60751 |
---|---|
Response time | 63% rt = 2,0 s |
Max. process pressure (static) | at 20°C: 250 bar (3.626 psi) depends on configuration |
Operating temperature range | PT 100: -200 °C ...600 °C (-328 °F ...1.112 °F) |
Max. immersion length on request | up to 96" (2439 mm) others on request |
Measuring principle | Resistance Temperature Detector |
Characteristic / Application | US style modular temperature assembly threaded process connection direct immersion style |
Thermowell / protection tube | without (not intended to be used with thermowell) |
Insert / probe | mineral insulated (MI), flexible PTFE-insulated, rigid |
Outer diameter protection tube / Insert | 1/8'' (3,18 mm) 3/16''(4,76 mm) 1/4'' (6,35 mm) 3/8'' (9,53 mm) |
Max. immersion length on request | up to 96" (2439 mm) others on request |
Material protection tube/ thermowell | Sensor sheath 316/316L |
Process connection | male thread: G1/2" NPT1/2" compression fitting: NPT1/8" NPT1/4" |
Tip shape | straight reduced |
Surface roughness Ra | Not defined |
Operating temperature range | PT 100: -200 °C ...600 °C (-328 °F ...1.112 °F) |
Max. process pressure (static) | at 20°C: 250 bar (3.626 psi) depends on configuration |
Accuracy | class A acc. to IEC 60751 class B acc. to IEC 60751 |
Response time | 63% rt = 2,0 s |
Integration head transmitter | yes (4 … 20 mA; HART; PROFIBUS PA; FOUNDATION FIELDBUS) |
Ex - approvals | transmitter only FM IS CSA IS FM/CSA IS |
Certification | SIL (transmitter only) |
Returns Policy