Endress+Hauser Micropilot FMR66B – 80 GHz radar sensor

Write a Review

REQUEST A QUOTE

Endress+Hauser Micropilot FMR66B – 80 GHz radar sensor
Accuracy+/- 3 mm (0.12 in)
Process temperature-40 … +130 °C (-40 … +266 °F)
Process pressure / max. overpressure limitVacuum...16 bar (232 psi)
Max. measurement distance50 m (164 ft)
Main wetted partsPVDF or PTFE
Measuring principleLevel radar solid
Characteristic / ApplicationFor simple applications:
Reliable, non-contact measurement of levels
in silos or storage tanks for bulk solids
SpecialitiesHeartbeat Verification + Monitoring, Bluetooth® Commissioning,
operation and maintenance with SmartBlue App,
HistoROM, RFID TAG for easy identification
Supply / Communication2-wire (HART/ PROFIBUS PA)
PROFINET with Ethernet-APL
Bluetooth® wireless technology
FrequencyW-Band (~80 GHz)
Antenna1-1/2" / 40mm encapsulated, PVDF
2" / 50mm Drip-off, PTFE
Accuracy+/- 3 mm (0.12 in)
Ambient temperature-40 … +85 °C (-40 … +185 °F)
Process temperature-40 … +130 °C (-40 … +266 °F)
Process pressure / max. overpressure limitVacuum...16 bar (232 psi)
Main wetted partsPVDF or PTFE
Process connectionThread:
G1-1/2", MNPT1-1/2"
Flange:
UNI DN80...DN150
Mounting bracket
Max. measurement distance50 m (164 ft)
CommunicationHART/ PROFIBUS PA
PROFINET with Ethernet-APL
Bluetooth® wireless
technology and app (optional)
Certificates / ApprovalsIEC Ex, ATEX, CSA C/US, EAC Ex, JPN Ex,
KC Ex, INMETRO Ex, NEPSI Ex, UK Ex
Safety approvalsSIL
Design approvalsEU Food Contact Material (EC) 1935/2004;
US Food Contact Material FDA CFR 21;
Declaration of Conformity ASME B31.3;
CRN approval
Marine approvalABS, LR, BV, RINA, DNV
OptionsDisplay, Customized settings,
App 'SmartBlue' for commissioning and operation via Bluetooth
Heartbeat for batch detection; Gas-tight implementation;
Overvoltage protection; PWIS free
Application limitsDK < 1.6
Reduction of the max. possible measuring range due to:
Media with poor reflective properties cone of repose
extremely loose surface of bulk solids, e.g. bulk solids with a
low bulk density during pneumatic filling buildup, especially of
moist products.
Alternative for these applications: FMR67B