Endress+Hauser Hydrostatic Level measurement Deltapilot FMB51

Write a Review

REQUEST A QUOTE

Endress+Hauser Hydrostatic Level measurement Deltapilot FMB51
AccuracyStandard 0.2%
Optional 0.1%
Process temperature-10°C...85°C
(14°F…212°F)
Pressure measuring range100 mbar...10 bar
(1.5 psi...150 psi)
Process pressure / max. overpressure limit40 bar (600 psi)
Main wetted partsAlloy C
316L
optional coating AuPt
Max. measurement distance100m (328ft) H2O
Material process membrane316L, AlloyC
Gold-Rhodium
Measuring cell100 mbar...10 bar
(1.5 psi...150 psi)
Measuring principleHydrostatic pressure
CharacteristicPressure transmitter for hydrostatic level measurement with flush mounted metallic Contite measuring cell:
Hermetically sealed, condensate-resistant, climatic-proofed and with lowest temperature influences
Rod version

Supply voltage4...20 mA HART
10,5...45 VDC (Non Ex):
Ex ia: 10,5...30 VDC
PROFIBUS PA:
9...32 VDC (Non Ex)
FOUNDATION Fieldbus:
9...32 VDC (Non Ex)



Reference AccuracyStandard 0.2 %
Optional 0.1 %
Long term stability0.05 % of URL/year
Process temperature-10°C...85°C
(14°F…212°F)
Ambient temperature-40°C...85°C
(-40°F...185°F)
Measuring cell100 mbar...10 bar
(1.5 psi...150 psi)
Smallest calibratable span10 mbar (1.45 psi)
Vacuum resistance0 mbar abs.
Max. Turn down100:1
Max. overpressure limit40 bar (600 psi)
Process connectionThread:
G1 1/2, MNPT1 1/2
Flange:
DN40...DN100,
ASME 2"...4",
JIS 10K
Material process membrane316L, AlloyC
Gold-Rhodium
Material gasketViton, EPDM, Kalrez, none
Fill fluidInert oil,
Synthetic oil
Material housing316L, Die-cast aluminum
Communication4...20 mA HART
PROFIBUS PA
FOUNDATION Fieldbus
Certificates / ApprovalsATEX, FM, CSA, CSA C/US, IEC Ex, INMETRO, NEPSI, UK Ex
Safety approvalsOverfill protection WHG
SIL
Design approvalsEN10204-3.1
NACE MR0175
Drinking water approvalsKTW/ NSF
SpecialitiesModularity to differential pressure and process pressure devices (replacable display, universal electronics)
Diagnostic functions
Measuring principleHydrostatic
Characteristic / ApplicationPressure transmitter for hydrostatic level measurement with flush mounted metallic Contite measuring cell:
Hermetically sealed, condensate-resistant and climatic-proofed
Rod version
SpecialitiesModularity to differential pressure and process pressure devices (replacable display, universal electronics)
diagnostic functions
Hermetically sealed Contite measuring cell (condensate-resistant and climatic-proofed)
Supply / Communication4...20mA HART:
10,5...45V DC
Ex ia: 10,5...30V DC
PROFIBUS PA /
FOUNDATION Fieldbus:
9...32V DC (Non Ex)
AccuracyStandard 0.2%
Optional 0.1%
Long term stability0.05 % of URL/ year
Ambient temperature-40°C...85°C
(-40°F...185°F)
Process temperature-10°C...85°C
(14°F…212°F)
Process pressure / max. overpressure limit40 bar (600 psi)
Pressure measuring range100 mbar...10 bar
(1.5 psi...150 psi)
Main wetted partsAlloy C
316L
optional coating AuPt
Process connectionThread:
G1 1/2, MNPT1 1/2
Flange:
DN40...DN100,
ASME 2"...4",
JIS 10K
Max. measurement distance100m (328ft) H2O
Communication4...20 mA HART
PROFIBUS PA
FOUNDATION Fieldbus
Certificates / ApprovalsATEX, FM, CSA, CSA C/US, IEC Ex, INMETRO, NEPSI
Safety approvalsOverfill protection WHG
SIL
Design approvalsEN 10204-3.1
NACE MR0175
Drinking water approvalsKTW/ NSF
OptionsSeparate housing
Initial device settings
Overvoltage protection
Application limitsIf pressurized, usage of two pressure transmitters to measure the differential pressure (electronic dP)
Observe ratio head pressure : hydrostatic pressure