AccuracyStandard 0.1%
Platinum 0.075%
Process temperature-20°C...130°C
(-4°F...266°F)
Pressure measuring range100 mbar...40 bar
(1.5psi...600psi)
Process pressure / max. overpressure limit60 bar (900 psi)
Main wetted partsCeraphire
Sealing
Alloy C276
316L
Max. measurement distance400 m (1312 ft) H2O
Material process membraneCeramic
Measuring cell100 mbar...40 bar
(1.5 psi...600 psi)
relative/ absolute
Measuring principleAbsolute and gauge pressure
CharacteristicSmart and reliable pressure transmitter with capacitive measuring cell and ceramic process isolating diaphragm Ceraphire)
Supply voltage4...20 mA HART
11,5...45V DC (Non Ex):
Ex ia: 11,5...30V DC
PROFIBUS PA:
9...32 V DC (Non Ex)
FOUNDATION Fieldbus:
9...32 V DC (Non Ex)





Reference AccuracyStandard 0.1%
Platinum 0.075%
Long term stability0.2% of URL/ year
0.4% of URL/ 5 years
0.5% of URL/ 10 years
Process temperature-40°C...+130°C
(-40°F...+266°F
+150°C for 1h
(+302°F for 1h)
Ambient temperature-40°C...+85°C
(-40°F...+185°F)
Measuring cell100 mbar...40 bar
(1.5 psi...600 psi)
relative/ absolute
Smallest calibratable span10 mbar (0.15 psi)
Vacuum resistance0 mbar abs.
Max. Turn down20:1
Max. overpressure limit60 bar (900 psi)
Process connectionThread:
G1/2...G2, R1/2, MNPT1/2
Flange:
DN25...DN80,
ASME 1"...4",
JIS 10K
Process connection hygienicTri-Clamp
DIN11851
DIN11864-1
NEUMO
Varivent N
SMS
DRD
Material process membraneCeramic
Material gasketViton, EPDM, NBR, Kalrez
Fill fluidNone, dry measuring cell
Material housingDie-cast aluminum,
AISI 316L
Communication4...20 mA
4...20 mA HART
PROFIBUS PA
FOUNDATION Fieldbus
IO-Link
Certificates / ApprovalsATEX, FM, CSA, CSA C/US, IEC Ex, INMETRO, NEPSI, UK Ex
Safety approvalsSIL
Design approvalsEN10204-3.1
NACE MR0175
Hygienic approvalsCoC ASME-BPE
3A, EHEDG
Marine approvalsGL/ ABS/ LR/ BV/ DNV
Drinking water approvalsNSF
SuccessorPMC51B
Measuring principleAbsolute and gauge pressure
Characteristic / ApplicationSmart and reliable pressure transmitter, with capacitive measuring cell and
ceramic process isolating diaphragm
(Ceraphire)
Supply / Communication4 ..20 mA HART:
11,5...45V DC
Ex ia: 11,5...30V DC
PROFIBUS PA
FOUNDATION Fieldbus
AccuracyStandard 0.1%
Platinum 0.075%
Long term stability< 0,1% of URL/ year
< 0,25% of URL/ 5 years
< 0,4% of URL/ 10 years
Ambient temperature-40°C...85°C
(-40°F...185°F)
Process temperature-20°C...130°C
(-4°F...266°F)
Process pressure / max. overpressure limit60 bar (900 psi)
Pressure measuring range100 mbar...40 bar
(1.5psi...600psi)
Main wetted partsCeraphire
Sealing
Alloy C276
316L
Process connectionThreads
Flanges (DIN, ASME, JIS)
Max. measurement distance400 m (1312 ft) H2O
Communication4...20 mA HART
PROFIBUS PA
FOUNDATION Fieldbus
IO-Link
Certificates / ApprovalsATEX, FM, CSA C/US, IEC Ex, INMETRO, NEPSI
Safety approvalsSIL
Design approvalsEN 10204-3.1
NACE MR0175, MR0103
Hygienic approvals3A, EHEDG
CoC ASME-BPE
Marine approvalGL/ ABS/ LR/ BV/ DNV
Drinking water approvalsNSF
OptionsLocal display
SuccessorPMC51B
Application limitsMeasuring cell: ceramics
If pressurized, possibly use differential pressure measurement with two pressure transmitters (electronic dp). Observe ratio head pressure : hydrostatic pressure