Endress+Hauser 71555090 iTHERM TrustSens Bluetooth and WirelessHART integration

Write a Review

REQUEST A QUOTE

Endress+Hauser 71555090 iTHERM TrustSens Bluetooth and WirelessHART integration
  • Cost reduction by saving calibration costs and reducing calibration cycles.

  • Risk reduction and elimination of undetected failures:

  • Higher process transparency

  • Higher product safety

  • The wireless integration of iTHERM TrustSens offers users in the life science and food and beverage industries optimized process verification with minimum effort.
    The product bundle consisting of the self-calibrating temperature sensor iTHERMTrustSens and the intelligent Bluetooth and WirelessHART adapter offers a simple and convenient way of reading out the calibration data and minimizing risks.
    • Easy accessible calibration status

    Measuring principleResistance Temperature Detector
    Characteristic / Applicationself-calibrating
    metric style
    compact temperature probe
    hygienic design
    life sciences, food & beverage
    Thermowell / protection tubewithout
    incl. thermowell
    incl. Tee-/elbow thermowell
    Insert / probewithout exchangeable insert
    Outer diameter protection tube / Insert6.0 mm (0.24'')
    9.0 mm (0.35'')
    12.7 mm (0.5")
    Max. immersion length on requestup to 900.00 mm (35.4'')
    Material protection tube/ thermowell1.4435 Delta Ferrite < 1%
    316L
    Process connectioncompression fitting
    weld in adapter
    clamp connections acc. to ISO 2852
    screwed pipe joint acc. to DIN 11851
    aseptic screwed pipe joint acc. to DIN 11864-1
    metallic sealing system
    thread acc. to ISO 228 for Liquiphant adaptor
    APV Inline
    Varivent
    Ingold
    SMS 1147
    Neumo Biocontrol
    TT411 elbow thermowell DIN 11865
    Tip shapestraight
    reduced
    Surface roughness Ra0.76 μm (29.92 μin)
    0.38 μm (14.96 μin)
    0.38 μm (14.96 μin) electropolished
    Operating temperature rangePt100:
    -40 °C to 160 °C (-40 °F to 320 °F),
    optional up to 190 °C (374 °F)
    reference point for automated calibration
    Max. process pressure (static)at 20 °C: 40 bar (580 psi)
    Response timet50 = 2.5 s
    t90 = 5.4 s
    Integration head transmitterno (4 to 20 mA signal, HART)
    Ex - approvalsCSA C/US IS, I/1+2/A-F
    CSA C/US General Purpose
    UK II1/2G Ex ia IIC T6 Ga/Gb, II1/2D Ex ia IIIC Da/Db
    ATEX IECEx II1/2G Ex ia IIC T6 Ga/Gb, II1/2D Ex ia IIIC T6 Da/Db
    Measuring principleWirelessHART
    FunctionIntelligent WirelessHART and/or Bluetooth® interface module for easy and fast connection to HART devices
    CertificationNon-hazardous area, ATEX, IEC Ex
    InputOne point-to-point with HART device
    OutputWirelessHART and/or Bluetooth® communication interface,
    Operating frequency: 2.4 GHz (ISM band),
    Transmission range under reference conditions:
    WirelessHART communication - up to 200 m (656 ft),
    Bluetooth communication - up to 40 m (131 ft)
    Auxiliary power supply / Loop power supplyLoop-powered 4 to 20 mA
    Dimensions (wxhxd)W x H x D: 146 mm x 42 mm x 42 mm
    (dimensions in mm 25.4 = 1 inch)
    SoftwareInternal software for reading data from HART field devices and communicating over WirelessHART and/or Bluetooth®
    OperationIntegral via DIP-switches,
    Cell Phone configuration via SmartBlue App and Bluetooth®,
    Field Xpert configuration via Bluetooth® or HART-modem,
    PC configuration via FieldCare and HART-modem,
    PC configuration via FieldCare and WirelessHART Gateway
    Operating Voltage24 V DC (min. 4 V DC, max. 30 V DC): min. 3.6 mA loop current required for start-up
    Voltage drop if internal HART communication resistor is deactivated:
    3.2 V in operation, < 3.8 V at start-up
    Voltage drop if internal HART communication resistor is activated (270 Ohm):
    < 4.2 V at 3.6 mA loop current, < 9.3 V at 22.5 mA loop current