Danfoss
132N4273 FC-202P630T4E54H4TGC3XXSXXXXALB4CXXXXD0
REQUEST A QUOTE
Frequency converter
FC-202P630T4E54H4TGC3XXSXXXXALB4CXXXXD0
VLT® AQUA Drive FC-202
(P630) 630 KW / 900 HP, Three phase
380 - 480 VAC, (E54) IP54 / Type 12
RFI class A1 (C2)
Safe Stop
Graphical Loc. Cont. Panel
Coated PCB, Mains Disconnect + Fuse
Latest release std. SW.
PROFINET MCA 120, MCB-114 VLT Sensor Input
No C1 option, MCB-107 24V DC backup
Frame: F3
Other options according to Model code
Model code :
FC-202P630T4E54H4TGC3XXSXXXXALB4CXXXXD0
Danfoss VLT® AQUA Drive is dedicated to water and wastewater applications. With a wide range of powerful sta.
Gross weight | 1017.3 kg |
Net weight | 1017 kg |
Volume | 0 l |
EAN | 5715253082585 |
VLT® AQUA DRIVE FC 200 SERIES
Product View (Switch) | GLBL | Global (Standard) |
Product Group | FC- | VLT® AQUA Drive FC- |
Series | 202 | 202 |
Power Rating | P630 | (P630) 630 KW / 900 HP |
Phase | T | Three phase |
Mains Voltage | 4 | 380 - 480 VAC |
Enclosure | E54 | (E54) IP54 / Type 12 |
RFI Filter | H4 | RFI class A1 (C2) |
Brake - Safe Stop | T | Safe Stop |
LCP | G | Graphical Loc. Cont. Panel |
Coating PCB | C | Coated PCB |
Mains Option | 3 | Mains Disconnect + Fuse |
Adaptation A | X | Standard Cable Entries |
Adaptation B | X | No adaptation |
Software Release | SXXX | Latest release std. SW. |
Software Language Pack | X | Standard Language Pack |
A Option | AL | PROFINET MCA 120 |
B Option | B4 | MCB-114 VLT Sensor Input |
C0 Option MCO | CX | No C0 option |
C1 Option | X | No C1 option |
C Option Software | XX | No software option |
D Option | D0 | MCB-107 24V DC backup |
Frame Size | F3 | F3 |
Typecode Part 1 | FC-202P630T4E54H4TGC | |
Typecode Part 2 | 3XXSXXXXALB4CXXXXD0 | |
Product Catalog | NO_VIEW | NO VIEW |
Power 150% (HO) [KW] | 560 | |
Power 110% (NO) [KW] | 630 | |
Height [mm] | 2204,0 | |
Width w/ no C options [mm] | 2000,0 | |
Depth [mm] | 606,0 | |
Depth with Option A/B [mm] | 606,0 | |
kVA | 776 | |
Power Loss NO [W] | 12512 | |
Power Loss NO [W] | 11595 | |
Power Loss HO [W] | 10649 | |
Power Loss HO [W] | 9414 | |
Continuous Current (NO) [A] | 1120 | |
Intermittent Current (NO) [A] | 1232 | |
Continuous Current (NO) [A] | 1050 | |
Intermittent Current (NO) [A] | 1155 | |
Continuous Current (HO) [A] | 990 | |
Intermittent Current (HO) [A] | 1485 | |
Continuous Current (HO) [A] | 890 | |
Intermittent Current (HO) [A] | 1335 | |
Calculated Gross Weight [kg] | 1017.3 | |
Calculated Net Weight [kg] | 1017 | |
Material Gross Weight | 1017.3 | |
Material Net Weight | 1017 | |
Plant from Orderline | F605 | |
Vendor | ERR01 | Cannot Determine Vendor |
Recommended Factory | ERR01 | Cannot Determine Vendor |
Modelcode01 | FC-202P630T4E54H4TGC | |
Modelcode02 | 3XXSXXXXALB4CXXXXD0 |