131N1095 Danfoss Vlt Hvac Drive 11kw Inverter Drive, 24a, Three Phase With A 380...480v Ac Supply Fc-102p11kt4p55h1xgx1oxsxxxxaxbxcxxxxdx

Write a Review

REQUEST A QUOTE

131N1095 Danfoss Vlt Hvac Drive 11kw Inverter Drive, 24a, Three Phase With A 380...480v Ac Supply Fc-102p11kt4p55h1xgx1oxsxxxxaxbxcxxxxdx
Danfoss 131N1095

Mains supply
Supply voltage 380...480V AC
Supply frequency 50/60 Hz
Displacement power factor (cos φ) near unity (>0.98)
Switching on input supply 1-2 times/min
Output data
Output voltage 0-100% of supply voltage
Output frequency 0-200 Hz (VVC+ mode), 0-400 Hz (U/f mode)
Switching on output Unlimited
Ramp times 1-3600 sec
Open/Closed loop 0-1000 Hz
Digital inputs
Programmable digital inputs 6 (two can be used as digital outputs)
Logic PNP or NPN
Voltage level 0-24 VDC
Pulse inputs
Programmable pulse inputs 1 (one of the digital inputs can be used for pulse inputs)
Voltage level 0-24 VDC (PNP positive logic)
Pulse input accuracy 0.1-110 kHz
Analogue input
Analogue inputs 2
Modes Voltage or current
Voltage level 0 V to +10 V (scaleable)
Current level 0/4 to 20 mA (scaleable)
Analogue output
Programmable analogue outputs 1
Current range at analogue output 0/4-20mA
Relay outputs
Programmable relay outputs 2 (240 VAC, 2 A and 400 VAC, 2 A)
Fieldbus communication Standard built-in: FC Protocol, N2 Metasys, FLN Apogee, Modbus RTU, BACnet embedded
Optional: LonWorks (MCA 108), BACnet (MCA 109), DeviceNet (MCA 104) Profibus (MCA 101) 


 

 

Danfoss New replacements for discontinued Danfoss drives

Returns Policy

Related Products

Top