131B1102 Danfoss Vlt Automationdrive Fc 301 0.75kw Inverter Drive 4.6a, Three Phase With A 200...240v Ac Supply Fc-301pk75t2e20h2bgcxxxsxxxxaxbxcxxxxdx

Write a Review

REQUEST A QUOTE

131B1102 Danfoss Vlt Automationdrive Fc 301 0.75kw Inverter Drive 4.6a, Three Phase With A 200...240v Ac Supply Fc-301pk75t2e20h2bgcxxxsxxxxaxbxcxxxxdx
Danfoss 131B1102

Mains supply
Supply voltage 200...240V AC
Supply frequency 50/60 Hz
True Power Factor (λ) 0.92 nominal at rated load
Displacement Power Factor (cos φ) near unity (> 0.98) 
Switching on input supply Maximum 2 times/min 
Output data 
Output voltage 0-100% of supply voltage 
Output frequency 0.2 -1000 Hz 
Switching on output Unlimited 
Ramp times 1-3600 sec 
Digital inputs 
Programmable digital inputs 4 (5) 
Logic PNP or NPN 
Voltage level 0 - 24 VDC
Analogue input 
Analogue inputs 2
Modes Voltage or current
Voltage level 0 to +10 V (scaleable)
Current level 0/4 to 20 mA (scaleable)
Pulse/encoder inputs
Programmable pulse/encoder inputs 1
Voltage level 0-24 VDC (PNP positive logic)
Digital output
Programmable digital/pulse outputs 1
Voltage level at digital/pulse output 0-24 VDC
Analogue output
Programmable analogue outputs 1
Current range 0/4-20 mA
Relay outputs
Programmable relay outputs 1
Cable lengths
Max. motor cable lengths 50 m (screened/armoured)
75 m (unscreened/armoured) 


 

 

Danfoss New replacements for discontinued Danfoss drives