Danfoss 131B1100
Mains supply | |
Supply voltage | 200...240V AC |
Supply frequency | 50/60 Hz |
True Power Factor (λ) | 0.92 nominal at rated load |
Displacement Power Factor (cos φ) near unity | (> 0.98) |
Switching on input supply | Maximum 2 times/min |
Output data | |
Output voltage | 0-100% of supply voltage |
Output frequency | 0.2 -1000 Hz |
Switching on output | Unlimited |
Ramp times | 1-3600 sec |
Digital inputs | |
Programmable digital inputs | 4 (5) |
Logic | PNP or NPN |
Voltage level | 0 - 24 VDC |
Analogue input | |
Analogue inputs | 2 |
Modes | Voltage or current |
Voltage level | 0 to +10 V (scaleable) |
Current level | 0/4 to 20 mA (scaleable) |
Pulse/encoder inputs | |
Programmable pulse/encoder inputs | 1 |
Voltage level | 0-24 VDC (PNP positive logic) |
Digital output | |
Programmable digital/pulse outputs | 1 |
Voltage level at digital/pulse output | 0-24 VDC |
Analogue output | |
Programmable analogue outputs | 1 |
Current range | 0/4-20 mA |
Relay outputs | |
Programmable relay outputs | 1 |
Cable lengths | |
Max. motor cable lengths | 50 m (screened/armoured) 75 m (unscreened/armoured) |